1. Home
  2. Understanding Compliance with the New UAE Fire and Life Safety Code

Understanding Compliance with the New UAE Fire and Life Safety Code

  • Date Published
Chapter 10, section 2.2 of the recently implemented UAE Fire and Life Safety Code addresses HVAC Systems and must be considered when deciding which HVAC products to use on a project.

Overview

Following the introduction of the UAE Fire and Life Safety Code, the Middle East HVAC industry has been introduced to a number of new phenolic pre-insulated ductwork products. It’s important to understand the tests and compliances that are required for each type of product by the UAE Fire and Life Safety Code.

The requirements outlined in table 10.1 part II state that Class 0 or Class 1 rigid or flexible air ducts tested in accordance with ANSI/UL 181 listing shall be permitted to be used for ducts when air temperature in the ducts does not exceed 250ºC or when used as vertical ducts serving not more than two adjacent stories in height.

Table 10.1 part III of the UAE Fire and Life Safety Code states that pipe and duct insulation and coverings shall have a maximum flame spread index of 25 without evidence of continued progressive combustion and a maximum smoke developed index of 50 when tested in accordance with ASTM E 84.

Talk to us

What can we help you with?
General Enquiry
Technical Enquiry
Specification Enquiry
Kingspan Insulation
About Us
Our Business
News Articles
Planet Passionate
Careers
Products
Building Insulation
HVAC Insulation
Services
Lunch and Learn
U-Value Calculations
Connect with Us
LinkedIn
Facebook
YouTube
Instagram

Cookie Policy & ControlTerms & Conditions of Website UseWebsite Privacy Notice

© 2026 Kingspan Holdings (IRL) Limited, All Rights Reserved