Kingspan BS 8414 Tested Systems

Various facade systems containing our products have met the requirements of BR 135 when tested to BS 8414. We publish all reports (both pass and fail). See below for more information, including specification details and downloadable classification reports. 

We fully recognise the concerns that are being experienced by many people as a result of the wider issue of safety of cladding systems in high-rise residential buildings. Building occupants who have a query or concern about the use of Kingspan Insulation products should contact their building owner / freeholder and request they fill out the form here and we will respond as soon as possible.

Systems containing Insulation Boards
Product update – Kingspan Kooltherm K15 Rainscreen Board

As part of a development project, Kingspan Insulation has made adjustments to the foil facer material of Kingspan Kooltherm K15. This change affects all Kooltherm K15 manufactured from the 09th March 2022 onwards. Please note that as a result, a number of BS 8414 system tests now have a corresponding assessment in lieu of test, in accordance with the guidance given in BS 9414: 2019. This assessment takes into consideration the change of facing material.

Kingspan BS 8414 Tested Systems

Kingspan Kooltherm K15 Taylor Maxwell Application Render

Kingspan Kooltherm K15 Rainscreen Board with Taylor Maxwell Tampa terracotta tiles

Tested Build-up

Knowledge Article5 min read
Kooltherm K15 Argeton application render

Kingspan Kooltherm K15 Rainscreen Board with Argeton Tampa terracotta tiles

Tested Build-up

Knowledge Article5 min read
Kooltherm K15 Alpolic fr acm application render

Kingspan Kooltherm K15 Rainscreen Board with ALPOLIC/fr ACM Panel

Tested Build-up

Knowledge Article5 min read
Kooltherm K15 Alpolic fr acm application render

Kingspan Kooltherm K15 Rainscreen Board with ALPOLIC/fr ACM Panel

Kooltherm K15 Rainscreen Board with ALPOLIC/fr ACM Panel

Knowledge Article5 min read
Kooltherm K15 Brick Application render

Kingspan Kooltherm K15 Rainscreen Board with bricks

Tested Build-up

Knowledge Article5 min read
Kooltherm K15 Eternit application render

Kingspan Kooltherm K15 Rainscreen Board with Eternit Equitone Natura panels

Tested Build-ups

Knowledge Article5 min read

Kingspan Kooltherm K15 Rainscreen Board with ALPOLIC A2 ACM Panel

Tested Build-up

Knowledge Article5 min read

Systems containing Insulated Panels

Systems which have NOT met the requirements of BR 135


This section contains reports of BS 8414 tests with systems that have failed to meet the requirements of BR 135. Please refer to the list above, as some of the combinations of materials tested below have met the requirements of BR 135 in specific system configurations.

100mm Kingspan Kooltherm K15 Rainscreen Board on SFS with Alpolic A2 ACM with panels 1150mm in height and 998m in width.

BS 8414-2: 2015 +A1:2017 test report: DLR1515 Rev.0

100mm Kingspan Kooltherm K15 Rainscreen Board with Dri-Design Aluminum Cassette.

BS 8414-2: 2015+A1:2017 test report: DLR1547 Rev.0

Vitracore G2 ACM with 180mm Rockwool Duo Slab Insulation

BS 8414-1:2015 + A1 :2017 test report: DLR1516 Rev.0

Classification Report as per BR135:2013 Annex A Tested as per BS 8414-1: 2015 + A1:2017: SR0894 Rev.0

100mm PIR Karrier Panel with Thermatile tile rainscreen

BS 8414-2: 2005 test report: 270772

160mm Kingspan Kooltherm K15 Rainscreen Board with Alpolic A2 ACM Cassette Panel.

BS 8414-2: 2015+A1:2017 test report: DLR1567 Rev.0

100mm Kingspan Kooltherm K15 Rainscreen Board with 10mm Trespa Meteon FR Panel.

BS 8414-1: 2015+A1:2017 test report: DLR1709 Rev.0

80mm Kingspan Kooltherm K15 Rainscreen Board with 13mm Trespa Meteon FR Panel.

BS 8414-2: 2015+A1:2017 test report: P114901 -1000

 140mm Kingspan Kooltherm K15 Rainscreen Board on SFS with CA Prime 7 Aluminium Cassette ​

BS 8414-2:2005 test summary report: P1000184-1002  (Non-UKAS Accredited)

160mm Kingspan Kooltherm K15 Rainscreen Board with Alpolic A2 ACM Panel

 BS 8414-2: 2015+A1:2017 Test Report: EUI-21-000272


For more information on the precise test build ups including more detailed drawings than available within the relevant report please contact our technical department technical@kingspaninsulation.co.uk

 

Archived Tests

The following tests do not have any BS 9414 assessment and therefore can only be used to support the use of product manufactured prior to the 18th October 2021. Kingspan are willing to work with any test report sponsors who wish to progress a BS 9414 assessment to incorporate the change of facing material. For more information, please contact highrisetechnical@kingspan.com.

Kingspan Kooltherm K15 Rainscreen Board with Booth Muirie BML 100-HP aluminium cassette panel

Test report BS 8414-1: 2015+A1 2017 - DLR1448 Download here

Classification report BR 135: 2013 - SR0810 Download here

Kingspan Kooltherm K15 Rainscreen Board with ALPOLIC A2 ACM Panel

Test report BS 8414-1: 2015+A1 2017 - P109971-1000 Download here

Classification report BR 135: 2013 - P109971-1001 Download here

Kingspan Kooltherm K15 Rainscreen Board with ALPOLIC A2 ACM Panel

Test report BS 8414-1: 2015+A1 2017 - P109973-1000 Download here

Classification report BR 135: 2013 - P109973-1001 Download here

Kingspan Kooltherm K15 Rainscreen Board with ALPOLIC/fr ACM Panel

Test report BS 8414-1: 2015+A1 2017 - DLR1453 Download here

Classification report BR 135: 2013 - SR0811 Download here

Kingspan Kooltherm K15 Rainscreen Board with Stofix brick cladding system

Test report BS 8414-2: 2005 - 303931

Classification report BR 135: 2013 - P100576-1000

Kingspan Kooltherm K15 Rainscreen Board with Gebrik cladding panels

Test report BS 8414-2: 2005 - P100838-1000 Download here

Classification report BR 135: 2013 - P100838-1001 Download here

Kingspan Kooltherm K15 Rainscreen Board with Argeton Tampa terracotta tiles

Test report BS 8414-1: 2015+A1 2017 – P119586-1000  Download here

Classification report BR 135: 2013 – P119586-1001  Download here

Archived Tests over five years old

Kingspan Kooltherm K5 External Wall Board with Alumasc render

Test Report BS 8414-1: 2015 + A1: 2017 - P112107-1000  Download here

Classification Report BR 135: 2013 - P112107-1001 297211  Download here

Archived Products/Systems

This product/system archive displays a list of discontinued products/systems. These are maintained to continue serving customers for informational purposes and are no longer available for sale.​

Kingspan Kooltherm K15 Rainscreen Board (with a black foil face) with Branco Michaela Granite stone cladding panels

Test report BS 8414-2: 2015+A1 2017 - EUI-18-FF-000131 Download here

Classification report BR 135: 2013 - EUI-18-FF-000131 Download here

Metallic Hook On Cassette

Test Report: BS 8414-2: 2005 - 297804 Download here

Classification Report: BR 135: 2013 Annex B - 299571 Download here 

Corium Brick Tile

Test Report: BS 8414-2: 2005 - P102340-1000 Download here

Classification Report: BR 135: 2013 Annex B - P102340-1002 Download here

Evolution

Test Report: BS 8414-2:2005 - 293939 Download here

Classification Report: BR135:2013 Annex B - 289585 Download here

QuadCore Architectural Wall Panel

Test Report BS 8414-2:2015 + A1:2017 - P107923-1000 Download here

Classification Report BR 135: 2013 Annex B - P107923-1001 - Download here

If you require any further information, please contact our technical department technical@kingspaninsulation.co.uk

 

Page reviewed: 01/05/2025

 

Talk to us

What can we help you with today?
BACK TO TOP
Contact us
Kingspan Insulation
Kingspan Technical Insulation
Kingspan Great Britain
Kingspan Insulation
Kingspan Technical Insulation
Legal information
Cookie Policy & Control
Terms & Conditions of Website Use
Website Privacy Notice
Modern Slavery Act Statement
Group Approach to Tax
Gender Pay Gap
Direct Marketing Consent Notice

© 2026 Kingspan Holdings (IRL) Limited, All Rights Reserved