AlphaCore Pad, K-Roc Rainscreen Slab & K-Roc Framing Slab (EUI-25-V-000553 - Revision 1)

  • Date Published
  • last Updated
  • Products
  • AlphaCore Pad
  • K-Roc Rainscreen Slab
  • K-Roc Framing Slab
AlphaCore Pad & K-Roc fire resistance tested system

Tested to BS EN 1364-1: 2015 (Fire resistance tests for non-loadbearing elements Part 1 – Walls). 

Tested Build-up

  • Two layers of 12.5 mm Gyproc Fireline, with a layer of Visqueen Class B FR vapour check

  • 100 mm K-Roc Framing Slab within steel frame

  • 12.5 mm Proctor cement particle board with a Proctor Wraptite breather membrane

  • 50 mm AlphaCore Pad

  • 120 mm K-Roc Rainscreen Slab

     

Results

Test results

Test: BS EN 1364-1: 2015

Report number: EUI-25-V-000553-Revision 1

Issue date: 2nd March 2026

Direction: Inside to outside

Integrity: 99 mins

Classification

Test: BS EN 13501-2: 2023

Report number: EUI-26-000060

Issue date: 7 April 2026

Direction: Inside to outside

Integrity: EI 90 mins

 

Downloads

Download the test report.

Download the classification report.

 

Field of direct application

The field of direct application defines the permissible variations that can be introduced to a tested specimen without requiring further testing or assessment. These modifications can be directly applied to tested systems and are generally considered conservative. 

Note that this test was carried out with the fire on the side with the two layers of 12.5 mm Gyproc Fireline. 

Please note that any number of these variations can be considered at the same time.

Height: the maximum permitted construction height is 3.04 m.

Wall thickness: the width of the construction can be increased without limitation.

Component thickness: the thickness of individual components may be increased.

Board and panel sizes: there may be a decrease in the linear dimensions of boards or panels, but not a decrease in thickness.

Stud spacing: the maximum stud spacing is 600 mm, but reduction in spacing is permitted.

Fixing centres: the distance between fixings may be reduced.

Horizontal joints: there may be an increase in the number of horizontal joints, of the type tested when tested with one joint not more than (500±150) mm from the top edge.

Vertical joints: there may be an increase in the number of vertical joints, of the type tested.

Any variations to the tested system beyond those outlined above could be considered as part of a technical fire assessment prepared in accordance with the PFPF Guidelines.

Looking for more information?

Book our CPD on fire safety for insulation

Our CPD covers the guidance, regulations and testing for insulation products. It takes a look at essential terminology for understanding how a fire develops and how products need to perform as a fire develops. 

Book here
an image of a building with rainscreen cladding

Useful Links

U-value calculator
Technical Information

U-value Calculator

We provide U-value calculations free-of-charge to show compliance with current Building Regulations, Standards and best practices. 

Kingspan Technical Services
Technical Information

Technical Services

Contact details for technical enquiries relating to insulation boards, cavity closers and membranes for Great Britain.

Virtual CPD image
Education & Training

CPDs & online learning

We have a number of in-person CPDs that can be booked, as well as 'Kingspan Learn' - our online training platform.

Talk to Us

What can we help you with?
Click here to request a sample
Stay Updated
Contact us
Kingspan Insulation
Kingspan Technical Insulation
Kingspan Great Britain
Kingspan Insulation
Kingspan Technical Insulation
Legal information
Cookie Policy & Control
Terms & Conditions of Website Use
Website Privacy Notice
Modern Slavery Act Statement
Group Approach to Tax
Gender Pay Gap
Direct Marketing Consent Notice
Customer Privacy Statement

© 2026 Kingspan Holdings (IRL) Limited, All Rights Reserved